Mitsubishi & Daikin Mini-Split Error Codes Explained
Mitsubishi M-Series blink codes and Daikin FTXF remote codes from the manufacturers' service manuals: what each one means, what's safe to try and when to call a pro.
Mitsubishi & Daikin Mini-Split Error Codes Explained
Mitsubishi Electric and Daikin ductless systems both report faults on their own, but in different ways. A Mitsubishi M-Series wall unit blinks its OPERATION INDICATOR lamp a set number of times. A Daikin wall unit stores a letter-number code that you pull up with the remote. Below are the manufacturer-published codes for two of the most common wall-mounted series in NYC apartments, what each one means, and which you can deal with yourself.
Each table covers only the series named in its heading. Mitsubishi and Daikin have built many indoor units, outdoor units and controllers over the years, and a code can mean something different on another model. Check the model number on the side of the indoor unit before you rely on a table.
Mitsubishi Electric M-Series (MSZ-GL / MSY-GL wall units)
Mitsubishi's service manual for the MSZ-GL and MSY-GL (OBH732) says to count how many times the upper OPERATION INDICATOR lamp blinks before the 2.5-second pause. When it detects one of these faults, the indoor fan stops and the lamp starts blinking.
| Blink pattern | What it means | What you can safely check | When to call |
|---|---|---|---|
| Blinks on and off every 0.5 s | Miswiring or serial signal fault: no signal from the outdoor unit for 6 minutes | Make sure the outdoor unit's disconnect and breaker are on | If it persists: indoor/outdoor wiring or a board |
| 2 blinks | Indoor coil or room temperature thermistor shorted or open | Nothing user-serviceable | Thermistor test and replacement |
| 3 blinks | Indoor fan motor: no speed feedback while the fan runs | Nothing user-serviceable | Indoor fan motor check |
| 4 blinks | Indoor control system: can't read the board's memory | Nothing user-serviceable | Indoor control board replacement |
| 5 blinks | Outdoor power system: compressor stopped on over-current or startup failure 3 times within a minute of starting | Nothing user-serviceable | Compressor/inverter and stop valve checks |
| 6 blinks | Outdoor thermistor shorted or open while the compressor runs | Nothing user-serviceable | Outdoor thermistor check |
| 7 blinks | Outdoor control system: can't read the inverter or outdoor board's memory | Nothing user-serviceable | Outdoor board replacement |
| 14 or more blinks | Other outdoor abnormality | Nothing user-serviceable | Outdoor unit failure-mode recall and diagnosis |
| Upper lamp lit, outdoor unit not running | Outdoor control system memory fault | Nothing user-serviceable | Outdoor board diagnosis |
| Upper lamp lit, lower lamp blinking (multi-zone MXZ outdoor units) | Indoor heads on the same outdoor unit are set to COOL (or DRY) and HEAT at the same time | Set all heads to the same mode | Not needed if it clears |
The last row is the one most NYC owners can fix themselves. On a multi-zone system, one bedroom set to HEAT and another set to COOL will stop the outdoor unit until everyone picks the same mode.
The manual also describes a failure mode recall function. It's a remote-control button sequence that replays the last stored fault even after the blinking has stopped. It's meant for technicians. If you start it, you have to release it afterwards (power-cycle the unit or press RESET on the remote), or the unit won't run properly. If you use a wired wall controller or a Wi-Fi adapter instead of the handheld remote, you may see a letter-number code instead of blinks. Check that controller's manual for the meaning.
Daikin wall-mounted FTXF / FTKF series
Daikin's service manual for the FTXF-B and FTKF-B (SiUS042425E) covers the ARC480 wireless remote. Hold the TIMER CANCEL button for 5 seconds until "00" appears. Then press TIMER CANCEL repeatedly. The remote steps through codes, and a long beep marks the one stored in the unit. A short beep or two quick beeps means that code isn't the one. Hold TIMER CANCEL for 5 seconds again to get back to normal mode.
| Code | What it means | What you can safely check | When to call |
|---|---|---|---|
| 00 | Normal | — | — |
| U0 | Refrigerant shortage | Nothing user-serviceable | Always. Leak search and charge by an EPA-certified technician |
| U2 | Low-voltage or over-voltage detected | Note any building power issues | If it repeats |
| U4 | Signal transmission error between indoor and outdoor unit | Make sure the outdoor disconnect and breaker are on, then power-cycle once | If it persists: wiring or boards |
| UA | Unspecified voltage between indoor and outdoor unit | Nothing user-serviceable | Usually a mismatched indoor/outdoor pairing or wiring |
| A1 | Indoor unit PCB abnormality | Power-cycle once | If it returns: board or pairing check |
| A5 | Freeze-up protection (cooling) or heating peak-cut | Clean the indoor filter; make sure nothing blocks the air path | Coil cleaning, thermistor or board |
| A6 | Indoor fan motor or related abnormality | Nothing user-serviceable | Fan motor diagnosis |
| C4 | Indoor heat exchanger thermistor abnormality | Nothing user-serviceable | Thermistor replacement |
| C9 | Room temperature thermistor abnormality | Nothing user-serviceable | Thermistor replacement |
| E1 | Outdoor unit PCB abnormality | Nothing user-serviceable | Outdoor board diagnosis |
| E5 | Compressor overload (OL) activated | Nothing user-serviceable | Thermistor, valves or refrigerant shortage |
| E6 | Compressor lock | Nothing user-serviceable | Compressor diagnosis |
| E7 | Outdoor DC fan lock | Look for leaves, ice or debris jamming the outdoor fan (power off first) | Fan motor or board |
| E8 | Input over-current detected | Nothing user-serviceable | Electrical diagnosis |
| F3 | Discharge pipe temperature control | Nothing user-serviceable | Refrigerant-side diagnosis |
| F6 | High-pressure control in cooling | Clear space around the outdoor unit | Dirty outdoor coil, fan or valves |
| H6 | Compressor position sensor abnormality | Nothing user-serviceable | Compressor/inverter diagnosis |
| L4 | Radiation fin (inverter heat sink) temperature rise | Check that the outdoor unit isn't boxed in | Outdoor fan or board |
| L5 | Output over-current detected | Nothing user-serviceable | Compressor/inverter diagnosis |
What's safe to try
- Clean the indoor filter. Daikin lists a clogged indoor filter as a likely cause of A5, and poor airflow drives many protective shutdowns on both brands.
- Clear the outdoor unit. On a terrace or roof, remove leaves, snow and anything stacked against the coil. Daikin lists cramped installation space and a dirty outdoor coil among the causes of F6.
- Check power. Make sure the outdoor disconnect and the breaker are on. Many "no signal" faults (Mitsubishi rapid blinking, Daikin U4) start with a tripped breaker.
- Power-cycle once. Turn the system off at the remote, switch the breaker off for a few minutes, then restore power. If the same code comes back, write it down and stop.
- On multi-zone Mitsubishi systems, match the modes on every indoor head.
Don't open the indoor or outdoor unit's electrical cover. Inverter boards can hold a dangerous charge after the power is off, and every refrigerant code (Daikin U0, E5 and F3, and Mitsubishi's 5-blink outdoor faults) needs an EPA-certified technician.
When to call a technician
- Any code that returns after one power-cycle and a filter cleaning.
- Refrigerant, compressor or inverter codes: Daikin U0, E5, E6, E8, F3, H6 and L5, and Mitsubishi's 5, 6, 7 and 14+ blink patterns.
- Sensor or fan motor codes: Daikin A6, C4, C9 and E7 (if the fan is clear), and Mitsubishi's 2- and 3-blink patterns.
- Ice on the indoor coil, water dripping from the indoor unit, or a burning smell along with any code.
Have the indoor and outdoor model numbers ready, plus the blink count or code. That alone often tells us which part to bring.
Our independent, EPA-certified technicians service Mitsubishi and Daikin ductless systems across Manhattan and the other four boroughs. We offer 24/7 emergency service and upfront pricing before any work starts. See Mitsubishi mini-split repair and Daikin ductless heat pump repair, or request service with your code.
Need Help With This?
Our licensed team is ready to help. Explore our services or request a technician.
Related Articles
Daikin vs Mitsubishi Mini-Splits: Which Is Cheaper to Repair in NYC?
Comparing Daikin and Mitsubishi mini-splits for NYC homes, reliability, parts availability, common failure points, and which is typically cheaper and easier to repair.
PTAC Error Codes: Friedrich, GE Zoneline and Amana Explained
What Friedrich, GE Zoneline and Amana PTAC error codes mean, taken from each manufacturer's manuals, plus which ones you can clear yourself and which need a technician.
Carrier & Bryant Furnace and Heat Pump LED Flash Codes
How to read the status LED on a Carrier or Bryant furnace or heat pump, what codes 13, 14, 31, 33 and others mean, and which ones you can safely handle yourself.